R455A Solstice® L40X
R-455A (Solstice® L40X)
Very Low GWP (148) A2L safety class alternative to R-404A, R-507A, R-407A, R-407F for all direct expansion refrigeration applications.
Features and Benefits
- Very low (<150) GWP –Sustainable and compliant with F-Gas legislation
- Good energy performance compared to R-404A – Lower indirect emissions and operating costs.
- Approved by many equipment manufacturers – Choice of new equipment available.
Packaging and Supply
- Climalife supply R-455A in 4.5kg, 10kg or 50kg returnable cylinders.
- Conforms to AHRI 700-2016 specifications.
- As R-455A is safety class A2L, it is important to use the right equipment for handling R-455A.
Why Choose Climalife?
Climalife are a key player in the distribution of refrigerants and other climate control products, with a nationwide distribution network and product knowledge that is second to none.
How does R-455A compare to R-404A?
R-455A has a similar cooling capacity compared to R-404A with improved energy efficiency compared to R‑404A. R‑455A does have the safety classification A2L due to its low flammability. R‑455A should only be used in systems compatible for use with low flammability refrigerants.
Full theoretical performance comparisons at customer specified conditions are available from Climalife on request.
Properties
Composition |
|
R-744/HFC-32/R-1234yf - 3/21.5/75.5% by mass |
|
Chemical Formula |
|
CO2/CH2F2/CF3CF=CH2 |
|
Molecular Mass |
87.45 |
||
Boiling Point (at 1 Atmosphere) |
-52.0°C |
||
Dew Point (at 1 Atmosphere) |
-39.2°C |
||
Saturated Liquid Density at 25°C |
1033.4 kg/m³ |
||
Saturated Vapour Density at 1.013bar |
4.747 kg/m³ |
||
Saturated Liquid Pressure at 25°C |
13.849 bar |
||
Saturated Liquid Pressure at 50°C |
24.433 bar |
||
Critical Temperature |
85.6°C |
||
Critical Pressure |
46.538 bar |
||
Critical Density |
454.9 kg/m³ |
||
Critical Volume |
0.00220 m³/kg |
||
Latent Heat of vapourisation at 1.013bar |
239.5 kJ/kg |
||
Thermal Conductivity of Liquid at 25°C |
76.9 mW/(m.K) |
||
Thermal Conductivity of Vapour at 25°C & 1.013bar |
13.7 mW/(m.K) |
||
Surface tension at 25°C |
5.50 mN/m |
||
Viscosity of Liquid at 25°C |
0.126 mPa.s |
||
Viscosity of Vapour at 25°C & 1.013bar |
0.012 mPa.s |
||
Specific heat of liquid at 25°C |
1.567 kJ/(kg.K) |
||
Specific heat of vapour at 25°C and 1.013bar |
0.8899 kJ/(kg.K) |
||
Cp/Cv ratio at 25° and 1.013 bar |
1.131 |
||
Lower Fammability Limit (LFL) in air (EN 378) |
0.431 |
||
Flash Point |
None |
||
ISO 817 / ASHRAE 34 Safety Classification |
A2L |
||
PED Fluid Group |
1 |
||
Ozone Depletion Potential (ODP) |
0 |
||
Global Warming Potential (GWP) IPCC AR4/IPCC AR5 |
148/146 |