R448A Solstice® N40
R-448A (Solstice® N40)
Lower GWP (1387) A1 safety class alternative to R-404A, R-507A, R-407A, R-407F for all direct expansion refrigeration applications.
Features and Benefits
- A1 (non-flammable) safety class – Ideal retrofit candidate for higher GWP refrigerants.
- 65% lower GWP than R-404A –More sustainable and compliant with F-Gas legislation.
- Good energy performance compared to R-404A – Lower indirect emissions and operating costs.
- Approved by many equipment manufacturers – Large choice of equipment available.
Packaging and Supply
- Climalife supply R-448A in 10kg, 19kg or 53kg returnable cylinders.
- Conforms to AHRI 700-2016 specifications.
Why Choose Climalife?
Climalife are a key player in the distribution of refrigerants and other climate control products, with a nationwide distribution network and product knowledge that is second to none.
How does R-448A compare to R-404A?
R-448A has a similar cooling capacity with improved energy efficiency compared to R‑404A. In many cases the compressor discharge temperature will not be a concern but for some low temperature applications, under the same operating conditions, R‑448A will exhibit a significantly higher compressor discharge temperature than R‑404A which, in a retrofit situation, may need to be managed.
Full theoretical performance comparisons at customer specified conditions are available from Climalife on request.
Properties
Composition |
|
HFC-32/HFC-125/R-1234yf/HFC-134a/HFO-1234ze(E) - 26/26/20/21/7% mass |
|
Chemical Formula |
|
CH2F2/CHF2CF3/CF3CF=CH2/CF3CH2F/CHF=CHCF3 (trans) |
|
Molecular Mass |
86.28 |
||
Boiling Point (at 1 Atmosphere) |
-46.1°C |
||
Dew Point (at 1 Atmosphere) |
-39.9°C |
||
Saturated Liquid Density at 25°C |
1097.2 kg/m³ |
||
Saturated Vapour Density at 1.013bar |
4.703 kg/m³ |
||
Saturated Liquid Pressure at 25°C |
12.876 bar |
||
Saturated Liquid Pressure at 50°C |
23.728 bar |
||
Critical Temperature |
82.7°C |
||
Critical Pressure |
45.945 bar |
||
Critical Density |
477.3 kg/m³ |
||
Critical Volume |
0.00210 m³/kg |
||
Latent Heat of vapourisation at 1.013bar |
241.5 kJ/kg |
||
Thermal Conductivity of Liquid at 25°C |
81.2 mW/(m.K) |
||
Thermal Conductivity of Vapour at 25°C & 1.013bar |
13.6 mW/(m.K) |
||
Surface tension at 25°C |
5.96 mN/m |
||
Viscosity of Liquid at 25°C |
0.138 mPa.s |
||
Viscosity of Vapour at 25°C & 1.013bar |
0.012 mPa.s |
||
Specific heat of liquid at 25°C |
1.555 kJ/(kg.K) |
||
Specific heat of vapour at 25°C and 1.013bar |
0.8497 kJ/(kg.K) |
||
Cp/Cv ratio at 25° and 1.013 bar |
1.141 |
||
Lower Fammability Limit (LFL) in air (EN 378) |
None |
||
Flash Point |
None |
||
ISO 817 / ASHRAE 34 Safety Classification |
A1 |
||
PED Fluid Group |
2 |
||
Ozone Depletion Potential (ODP) |
0 |
||
Global Warming Potential (GWP) IPCC AR4/IPCC AR5 |
1387/1273 |